78
CT2 delay time setting
Same as CT1 delay time setting
About control loop abnormal alarm
When the targeted output of a control loop abnormal alarm is ON, if current
detected by CT is lower than the allotted event's operating point. (Setting Value of
a basic screens, event operating point setting screen) alarm output is issued as
breaking alarm.
When the targeted output is OFF, if detected current is higher than the allotted
event's operating point(short-circuit, earth fault, etc.)
Mode 11 lead screen
6-6-12.
Mode12 Communication setting screen
No display when communication function not installed Refer to Communication manual.
6-6-13.
Mode13 Servo out setting screen
No display when Servo setting function not installed. Refer to Servo setting manual.