Out2 PID common character setting screen
Initial value:
Setting range:
、
Explanation of 2 output-characteristics figure
Two output characteristics is shown in the following figure.
◎ Conditions: P operation, manual reset (
) = -50.0%
1) OUT 1 RA (heating) ・OUT 2 DA (cooling) operation
control output 1 (RA characteristics)
control output 2 (DA characteristics)
output 100%
output 0%
▲
△
▲
-DB
DB = 0
+DB
△ : Setting Value (SV) ▲: DB (dead band)
2) OUT 1RA (heating)・ OUT 2 RA (heating)
control output 1 (RA characteristics)
control output 2 (RA characteristics)
output 100%
output 0%
▲
△
▲
-DB
DB = 0
+DB
△ : Setting Value (SV) ▲: DB (dead band)