66
Event 1 differential-gap setting screen
Initial value : 5Digits
Setting range : 1~9999 Digits
ON-OFF differential gap of event 1 is set
Not displayed, when the event 1 mode are as follows.
~
Being initialized if measuring range, scaling, and unit are changed.
Event 1 standby operation setting screen
Initial value :
Setting range :
, ,
:No standby operation、
: standby-operation only at the time of a power-
on. :Standby-operation in the following cases. ;At the time of power-on. When
each alarm's operating point is changed, When deviation alarm's SV is performed,
When RUN/STBY (RST) is switched, When AUTO/MAN is switched. Not displayed,
when the event 1 mode are as follows.
~
Being initialized if measuring range, scaling, and unit are changed.
Event 1 latching setting screen
Initial value:
Setting range:
、
When latching is set as
, once event is output, even if event is OFF state
event output state is held. Not displayed when event 1 mode is
Being
initialized if measuring range, scaling, and unit are changed.
Event 1 output characteristics setting screen
Initial value:
Setting range:
、
: normal open
: normal closing.
Not displayed when event 1 mode is
Note: If
is chosen, relay turns to ON about 1.5 seconds later when power
source is switched on, and turns to OFF in event output range.
EV1 setting lead screen