6-4 Explanation of each basic screen
Basic screen
Executed SV
Initial value
Sensor input : 0
Linear input : Lower limit of scaring
Setting range
Sensor input : Within measuring range
Linear input With in scaring range
Within SV limiter besides
Targeted value (PV) is displayed on the upper row as 5-digit, and target value (SV) is
displayed on the lower row also as 5-digit.
(Notes: hereinafter, measured value and targeted value are referred to as"PV" and"SV")
At the time of FIX, execution SV is displayed and change of setting is possible.
PROG's SV is just displayed, and change of setting is impossible.
During AT execuiting and Key lock level 2-4 are set, setting is impossible
At the time during AT and key lock level 2-4 is set, change of setting impossible.
Execution Program No. can be changed by pressing
at the RST in Program.
When no key operation 3 minutes or more, screen will be shifted to basic screen or the
screen of DI super key lock.
When measuring range, unit and scaling value changed, parameter will be initialized.
Action Mode 1
Action Mode 2
3 sec
3 sec
Initial value :
(Reset)
Setting range:
Control stop (Output Off)
(RUN)
conduct of control operation
Initial value:
Setting range:
,
During no operation the display will be
(Program) or
(FIX).
Choose
key and decided by
key then Monitor LED's RUN lights up to start control operation.
Choose
(
)by
key, Decide by
key, Then Monitor LED's RUN lights off
and becomes control stop [Output OFF (0%)] conducting.
Priority is given to DI function, when RUN is allotted to external control input. DI. Key
operation cannot be performed unless allotment is canceled.