34
SI 580E DIN SIZE WEIGHING CONTROLER
www.sewhacnm.co.kr
◆ Weighing Mode 3 – Packer Mode 1
2 Step control Packer Mode -F21 – 03 Setting
– Relay “ON” when weight reaches set value
- Relay “ON”
Within “EMPTY” range
Ex) When input set value as SP1(Target) = 1000, SP2(Drib) = 500, Empty range = 10,
SP3(free fall) = 0
Start Input : SP1, SP2 will be “ON”. Empty Range ≥10 , SP4 will be “OFF”.
Current weight will be reaches to (SP1-SP2=800) value, SP2 will be “OFF”.
Current weight will be reaches to SP1, (SP1-SP3=990) , SP1 will be “OFF”.
SP3 will be “ON” after SP1 off and delay during the “t1” time.
※
T1 = Finish Relay Output delay time, T2= Finish Relay output duration time
Relay Output
Relay
Contents
Relay
Contents
OUT 1
(Target)
Input “RUN” : “ON”
Current weight = Target - SP3 ”OFF”
OUT 2
(Drib)
Input “RUN” : “ON”
Current Weight = Target –
SP2 ”OFF”
OUT 3
(Finish)
After reaching target value
After “t1” time,
“ON” during “t2” time
OUT 4
(Empty)
Within “EMPTY(F80 settin
g)” range “ON”
WEIGHT