Assignment of optional plug connectors
Electrical installation
5.10.2 X5131: Digital inputs/outputs
The following table shows information about this connection:
Function
Digital inputs/outputs for MOVIGEAR
®
MotionControl
Connection type
M23, P insert 12-pole, SpeedTec-capable, Intercontec, female, 0°-coded
Wiring diagram
2264820107
Assignment
No.
Name
Function
Motion control inputs
DIP switch S2/3 = OFF
Function
Local mode
DIP switch S2/3 = ON
1
DI01
DI01 sensor input
CW/stop
2
DI02
DI02 sensor input
CCW/stop
3
DI03
DI03 sensor input
Setpoint f1/f2
4
DI04
DI04 sensor input
Changeover
Automatic/local mode
5
n.c.
Not connected
Not connected
6
n.c.
Not connected
Not connected
7
n.c.
Not connected
Not connected
8
+24V_O
Reserved
DC 24 V output
9
0V24V_O
Reserved
0V24 reference potential
10
0V24V_SEN
0V24 reference potential for sensors
Must be supplied via terminals X7.4
Reserved
11
+24 V_SEN
DC 24 V sensor supply
1)
Must be supplied via terminals X7.3
1) see operating instructions, chapter "Connecting MOVIGEAR
®
drive units"
Reserved
12
FE
Equipotential bonding/functional ground
Equipotential bonding/functional
ground
9
1
2
7
6
5
11
12
3
4
8
10
INFORMATION
Use actuator/sensor distributors with 4 slots for the sensor inputs. Use the DC 24 V
output only for local mode.