140
Operating Instructions – MOVIGEAR® SNI-B
8
Description of application option parameters
Parameters
Analog input AI10
index 9619.36
Analog input AI10 of the application option.
You can activate the analog input using DIP switch S1/1 of the application option (acti-
vated = DIP switch set to "ON").
The scaling is:
Voltage input: 0 V
Ⳏ
0 digit
10 V
Ⳏ
32767 digits
Current input: 4 mA
Ⳏ
0 digit
20 mA
Ⳏ
32767 digits
< 4 mA
Ⳏ
–1 (wire breakage detection)
You set the mode of the analog input using DIP switch S3/3.
If you set the current input mode using DIP switch "S3/3 = ON", then you have to activate
the current resistor using DIP switch "S3/4 = ON".
Voltage input mode
S3/3 = OFF
S3/4 = OFF
Current input mode S3/3 = ON
S3/4 = ON
Application option outputs
Digital output
DO10
index 9619.112,
bit 0
Digital output DO10 of the application option.
You can activate the digital output using DIP switch S1/4 of the application option
(activated = DIP switch set to "ON").
Analog output
AO10
index 9619.123
Analog output AO10 of the application option
The scaling is:
32767 digits
Ⳏ
20 mA
0 digit
Ⳏ
4 mA
You can activate the analog output using DIP switch S1/3 of the application option
(activated = DIP switch set to "ON").
Display of application option DIP switch settings
DIP switch
configuration
index 10453.12,
bits 0 to 10
The parameter indicates the DIP switch configuration of the application option.
00
I