Operating Instructions – MOVIGEAR® SNI-B
6
Description of DIP switches
Startup
6.3.2
Description of the DIP switches
DIP switches S1/1
to S1/4
Setting the SNI address
These DIP switches are used to set the SNI addresses of MOVIGEAR
®
drive units. You
can set addresses from 0 to 9. Other settings are not permitted.
DIP switches S2/1
to S2/2
Setting the operating mode
This DIP switch is used to set the operating mode of the MOVIGEAR
®
drive unit. It de-
termines how the unit is controlled.
When using MOVIFIT
®
SNI, the operating mode must be set to "SNI-SEWOS", when
using MOVIFIT
®
FDC SNI, it must be set to "VARIABLE".
DIP switch S2/3
Use of the motion control inputs
Use this DIP switch to determine the function of the motion control inputs (accessible
only via optional M23 plug connector).
• When DIP switch S2/3 is set to "OFF", the motion control inputs are used for con-
necting and evaluating sensors. It is not possible to control the actuator via the mo-
tion control inputs.
• When DIP switch S2/3 is set to "ON", the motion control inputs can be used for local
mode:
SNI address
0
1
2
3
4
5
6
7
8
9
S1/1
–
X
–
X
–
X
–
X
–
X
S1/2
–
–
X
X
–
–
X
X
–
–
S1/3
–
–
–
–
X
X
X
X
–
–
S1/4
–
–
–
–
–
–
–
–
X
X
X = ON
–
= OFF
Mode
MOVIFIT
®
SNI
(SNI-SEWOS)
Reserved
Reserved
MOVIFIT
®
FDC
(VARIABLE)
S2/1
–
X
–
X
S2/2
–
–
X
X
X = ON
–
= OFF
Motion control inputs
Functionality with DIP switch S2/3 = ON
Motion control input 1
CW/stop
Motion control input 2
CCW/stop
Motion control input 3
Setpoint selection n_f1 / n_f2
Motion control input 4
Local/automatic