11
Startup with EtherNet/IP™
Setting up the EtherNet/IP scanner
Manual – MOVI-C
®
CONTROLLER progressive UHX65A-M
46
Configuring the EtherNet/IP™ scanner network
•
Adjust the EtherNet/IP™ and network settings to your requirements in the "Gen-
eral" tab.
36123627915
•
The default setting of the bus cycle task "Use parent's bus cycle settings" is not al-
ways the optimal configuration. For the operation of the fieldbus, select an appro-
priate task from the task configuration or create a new task according to the follow-
ing example: cyclic task with a call interval of 4 or 10 ms and medium priority
When planning the application and the task configuration, please note that the pro-
cessing of the fieldbus stack takes approx. 300 – 400 µs and the execution of the
task is blocked for this period.
Further settings may be required for the respective case of application.
36123930123