5.3.7
Line contactor
NOTICE
Non-compliance with the minimum switch-on/switch-off times.
Damage to the device.
• Keep the supply system switched off for
10
s before switching the power back
on.
• Do not switch the supply system off and on more than once per minute.
• Use only a contactor of utilization category
AC‑3 (EN
60947-4-1) as a line con-
tactor.