6
Startup
Connecting the engineering PC and MOVI‑C® FIELD CONTROLLER
Operating Instructions – MOVI-C
®
FIELD CONTROLLER standard/advanced
104
6.5
Connecting the engineering PC and MOVI‑C
®
FIELD CONTROLLER
Connecting
the
engineering
PC and
MOVI‑C® FI
ELD
CONTROLL
ER
To ensure that the engineering PC can communicate via the X4224 engineering inter-
face with the
MOVI‑C
®
FIELD CONTROLLER via Ethernet, both the devices must be
connected in the same local network. For this purpose, the IP address parameters of
the engineering PC must be set to the local network. The default IP address(es) of the
Ethernet communication interface(s) can be found in chapter "DIP switch
Proceed as follows:
1. Open the settings for the network via the Windows control panel.
2. Double-click on the adapter that is physically connected to the X4224 engineering
interface of the
MOVI‑C
®
FIELD CONTROLLER.
3. Select the Internet protocol version 4 "TCP/IPv4" in the adapter properties.
4. Enter the IP address parameters of the engineering PC in the Internet protocol
properties. Note that the IP address of the engineering PC is different from the IP
address of all other network stations and is therefore unique. The network address
(in this case, the first
3‑address
blocks) for all network stations must be identical
and the station address (in this case, the last address block) of the engineering PC
must be different from the network address of all other stations.
18014415915164555
ð
In this example, the IP address of the engineering PC is: 192.168.10.38
26872137/EN – 12/2021