Manual – DFE32B Fieldbus Interface PROFINET IO
5
Startup procedure for MDX61B with DFE32B option
Project Planning with PROFINET
Step 2: Configuring PROFINET
1. Start the control manufacturer's software to configure the hardware (e.g. STEP 7-
HWKONFIG).
2. Install the GSD file if necessary (
→
section "Preliminary work")
3. Check whether PC and control are located in the same subnetwork:
– Are the IP addresses of PC and CPU identical up to the lowest byte?
– Is the subnet mask identical?
4. Check whether a TCP/IP communication can be established with the controller.
5. Carry out the PROFINET configuration according to this manual.
– Assign PROFINET device name
– Assign IP configuration if necessary
– Perform process data configuration
– Load the project planning to the controller
6. The BUS FAULT LED of the DFE32B option is off when PROFINET is successfully
configured. Process data is now being exchanged.
7. Extent control program and set up process data exchange to MOVIDRIVE
®
B.
8. Start MOVITOOLS
®
MotionStudio and open a new project. Set up "Ethernet" as
communication interface.
– Alternatively, MOVITOOLS
®
MotionStudio can be operated via serial communi-
cation with USB11A. Connect PC with MOVIDRIVE
®
B.
9. Perform a unit scan.
10.Select MOVIDRIVE
®
B, make a right mouse click and choose [Diagnostic] / [Bus
monitor] from the context menu. Check whether the project data exchange between
control and MOVIDRIVE
®
is working.
11.Switch on the supply voltage and enable MOVIDRIVE
®
B at the terminals (DI00=1).
Activate unit enable via control word 1 = 0x0006 .
– If MOVIDRIVE
®
B remains in "No Enable" condition, check terminal assignment
(parameter group P60x) and supply further binary inputs with DC 24 V if required.