![SEW-Eurodrive DFE32B PROFINET IO Скачать руководство пользователя страница 119](http://html1.mh-extra.com/html/sew-eurodrive/dfe32b-profinet-io/dfe32b-profinet-io_manual_1250328119.webp)
Manual – DFE32B Fieldbus Interface PROFINET IO
119
9
Communication via Ethernet
MOVITOOLS® MotionStudio – Operation
3. Enter the IP address in the input field [2] and click the [OK] button.
9.9.4
Communication parameters for SMLP
The following table describes the communication parameters for SMLP:
9.9.5
Communication ports used
The following table describes the communication ports used by MOVITOOLS
®
MotionStudio:
Communication parameters
Description
Note
Timeout
Waiting time in ms that the client
waits for a response from the
server after it has made a
request.
•
Default setting: 1000 ms
•
Increase the value as
required if a delay in commu-
nication is causing malfunc-
tions.
Broadcast IP address
IP address of the local network
segment
within
which the unit
scan is carried out.
In the default setting, the unit
scan only detects units that are in
the local network segment.
IP address of SMLP server
IP address of the SMLP server or
of other units that are to be
included in the unit scan but are
outside
the local network seg-
ment.
•
Enter the IP address of units
that are to be included in the
unit scan but are
outside
the
local network segment.
•
Enter the IP address of the
SIMATIC S7 control, if you
are operating an indirect
Ethernet to PROFIBUS com-
munication via SIMATIC S7.
Excluded IP address
IP addresses of units that should
not
be included in the unit scan
Enter the IP address of units that
should
not
be included in the unit
scan. This can be units that are
not ready for communication (for
example because they have not
been started up yet)
Use
No. of the communica-
tion port
Description
ETH server
300
For using a PC as Ethernet gateway with
the program "
ETHServer.exe
"
SEW communication server
301
For communication between
MOVITOOLS
®
MotionStudio and the
SEW Communication Server
Offline data server
302
For communication of
MOVITOOLS
®
MotionStudio in offline
mode
MOVIVISION
®
server
303
For communication with a PC with active
MOVIVISION
®
server
MOVI-PLC
®
visualization
304
For communication between MOVI-PLC
®
and the 3D simulation of
MOVITOOLS
®
MotionStudio
TCI server
305
For communication via TCI
EcEngineeringServer remote
control (in preparation)
306
For direct communication (without master)
with SEW EtherCAT slaves
EcEngineeringServer mailbox
gateway (in preparation)
307
For direct communication (without master)
with SEW EtherCAT slaves