Manual – DFE32B Fieldbus Interface PROFINET IO
45
5
Setting the MOVIDRIVE® MDX61B
Project Planning with PROFINET
5.3
Setting the MOVIDRIVE
®
MDX61B
To control the drive inverter via PROFINET, you must first switch the drive inverter to
control signal source (P101) and setpoint source (P100) = FIELDBUS. The FIELDBUS
setting means the drive inverter parameters are set for control and setpoint entry via
PROFINET. The MOVIDRIVE
®
drive inverter then responds to the process output data
transmitted from the master programmable controller.
The parameters of the MOVIDRIVE
®
drive inverter can be set straight away via
PROFINET without any further settings once the PROFINET option card has been in-
stalled. For example, all parameters can be set by the master programmable controller
after power-on.
Activation of the control signal source and setpoint source FIELDBUS is signaled to the
machine control using the "Fieldbus mode active" bit in the status word.
For safety reasons, you must also enable the drive inverter at the terminals for control
via the fieldbus system. Therefore, you must wire and program the terminals in such a
way that the drive inverter is enabled via the input terminals. For example, the simplest
way of enabling the drive inverter at the terminals is to connect the DIØØ (function
/CONTROL INHIBIT) input terminal to a DC +24 V signal and to program input terminals
DIØ1 ... DIØ3 to NO FUNCTION.