Chapter D - Setting to work
Rev. A 10-99
DigiDrive Manual Series 2000 / 4000
Pg 63
Servo Dynamics Corp. 21541-D Nordhoff St. Chatsworth, CA 91311 www.servodynamics.com
4.1
How to set the resolver shift angle parameter
This operation should be done only when the resolver shift angle is unknown. In this case, the
setting procedure is as follows :
D
A)
Click on the « Regulation loop » icon and click on the « M » (motor) button in the
« Regulation loop » window.
D
B)
Set the « Maximum motor current » to 25% of the Nominal motor current in the « Motor
features » window.
D
C)
Click on the « Speed command » button in the « Regulation loop » window. Then click on
the « Single-polarity periodical pulse mode » button in the « Automatic command mode »
window.
Enter :
A = 120 rpm
tx = 200 ms
T = 200 ms
And click on the « Run » button.
D
D)
Click on the « Resolver » button in the « Regulation loop » window and Enable the drive.