11
Remote Digital
Interface
Connections:
ACC 065
Field Wiring
ACC 070
Field Wiring
ACC 071
Field Wiring
Remote Control Panel Interface, full
function remote control for monitor
14 or 16 AWG (Line voltage supply to
transformer)
18 or 22 AWG (24 VAC from
transformer to Remote)
18 or 22 AWG (twisted shielded wire for
rs-485 connection to monitor)
COMM LINK, PC to refrigerant monitor
interface
Wall outlet transformer (Provides 24
VAC to COMM LINK)
Cable and Adapters (rs-232 interface
from COMM LINK to PC)
18 or 22 AWG
(twisted shielded wire for rs-485
connection to monitor)
MODEM, Interface for Remote PC
Connection to COMM LINK
Wall outlet transformer (Provides 24
VAC to Modem)
Cable and Adapters (rs-232 interface
from Modem to COMM LINK)
Optional – Purchased separately from monitor, provides
complete remote interface for all monitors in building via
rs-485 interface (subject to cable length limitations of rs-
485), powered by 24 vac transformer
Provided by customer, Install in accordance with NEC and
local codes
Optional – Purchased separately from monitor, provides
complete remote interface from PC to all monitors in
building via rs-485 interface (subject to cable length
limitations of rs-485), used with Windows based software
provided with COMM LINK
Provided with COMM LINK, if multiple devices are
powered by the same transformer, polarity must be
maintained the same for all devices
Provided with COMM LINK
Provided by customer, Install in accordance with NEC and
local codes
Optional – Purchased separately from monitor, provides
connection via phone line from PC to COMM LINK, allows
off premises remote PC to dial in to all monitors in building
via rs-485 interface (subject to cable length limitations of
rs-485), Requires COMM LINK and Windows based
software provided with COMM LINK
Provided with ACC 071, if multiple devices are powered
by the same transformer, polarity must be maintained the
same for all devices
Provided with ACC 071
Содержание IR-SNIF-MC-1
Страница 54: ...05 21 2008 ...