17
control interface. Used in conjunction with
the ACC 065 Remote Control Panel
Interface, the RS-485 interface allows for
complete remote control and monitoring of
multiple refrigerant monitors in the same
facility.
RS-485 digital connections are as follows:
1. Use
twisted
wire
for
RS-485
connection, either twisted triple wire,
or four conductor twisted wire.
Shielded cable is preferred, but not
always required.
2. Route twisted pair wire into the
monitor and along the wire harness
from the back-plate to the TB3 on
the back-plate. Secure the twisted
wire periodically to the wire harness
using tie wraps.
3. Connect the transmit conductor to
TB3-6.
4. Connect the receive conductor to
TB3-8.
5. If twisted triple wire is used, connect
the
remaining
wire
to
TB3-7,
reference or shield ground.
6. If two twisted pairs are used, connect
one conductor from each pair to
TB3-7, reference ground or shield.
Custom Control Inputs/Outputs:
The IR-
SNIF-MCD monitor has the capability to be
programmed for additional optional inputs
or outputs. The control circuit in the
monitor is versatile and can accommodate
additional analog or discrete measurement
and control signals. This circuit also has
the capability to provide additional discrete
control signals. Please contact SenTech
Corporation technical support to determine
whether specific requirements can be
provided.