31
monitor time outs and returns to normal
operation.
Auto zero:
Auto zero measures the fresh
air (refrigerant free) zone between each
zone. Auto zero takes approximately 24
seconds under normal conditions. If the
monitor senses a high concentration of
refrigerant, the Auto zero measurement
time is extended to approximately 45
seconds.
Auto Sample:
Auto sample mode is the
normal measurement mode of the monitor.
It displays the PPM level beings measured,
the refrigerant and the current time. If the
Horn relay has been energized, the fourth
line will instruct the operator to press the
"RESET" key to silence the horn. If the
monitor is in alarm, the fourth line will
instruct the operator to press the reset key
to clear alarms.
Leak Wait:
When the monitor is in Auto
sample mode and first senses a change in
PPM, it enters Leak Wait mode. This
ensures the monitor truly detects a leak
before activating the Low Alarm relay and
the Main Alarm relay. The length of the
wait period depends upon the difference
between the concentration level and the
alarm trip point. The larger the difference,
the shorter the wait time. If the
concentration falls below the alarm trip
point, the system will determine that it was
a transient, and return to normal operation.
Fault Mode:
When the monitor detects a
fault condition, it will enter fault mode. The
Main relay will energize and "Trouble
Alarm" will be displayed in the third line of
the display.
Alarm Modes:
When the monitor has
sensed concentrations above the alarm trip
points, the associated relays will be
energized. The Low, Main and High relays
will be energized if the measured ppm level
has exceeded the corresponding alarm
levels. The Horn relay will be energized
depending on its programming. The
monitor can be set up to energize the Horn
relay when the Low alarm is activated, the
Main alarm is activated or the High alarm is
activated. This is programmed via the
System Setup menus described later in this
document.
If an alarm is activated, the fourth line in the
operational screens will change to instruct
the operator how to clear the alarm. When
the "RESET" is pressed, the monitor will
switch directly to the Alarm Status screen
described later in this appendix.
If the monitor has also energized the Horn
relay, it can be silenced by pressing the
"RESET" key. The fourth line in the
** Auto Zero**
Timer 24 12:00
Press ENT for Menu
Auto Sample AREA 1
PPM 0 12:00
R-134A
Press ENT for Menu
LEAK WAIT AREA 1
PPM 0 12:00
R-134A
Press ENT for Menu
Auto Sample AREA 1
PPM 0 12:00
Trouble Alarm
Press ENT for Menu