22
LOW and MAIN alarms are self-resetting or
are latched. If the LATCH FLAG is set to 0,
the alarms will function as a conventional
latching alarm. If the LATCH Flag is set to
1, the LOW and MAIN alarms will function
as self-resetting alarms. The HIGH alarm
will always be a latching alarm.
NOTE: The ASHRAE-15 standard specifies
that an alarm relay must be latched, but
that if more than one alarm level is
provided, the additional alarms may be self-
resetting. Care must be used when
implementing this feature, as the alarm
level that corresponds to the ASHRAE-15
required alarm MUST be a latching alarm.
If there are any questions regarding the
correct implementation of this feature, call
SenTech technical support.
Press the “ENT” key to move the cursor to
the next entry. When all entries have been
viewed, press the “ENT” key again to return
to the previous menu. The monitor should
again display the system setup menu.
Press the right arrow ”->” key to access the
second system setup screen.
Press the “4” key to set the date and time.
The program time/date screens allows the
user to set the day of the week, hour,
minute, month, day, and year for the real
time clock (RTC) in the controller. Entering
information, or pressing the “ENT” key will
move the cursor down to the next entry.
Note that the RTC operates on a 24-hour
clock. For example to enter 2 PM, enter the
hour as 14, rather than 2.
When the date and time have been
entered, press the “ENT” key to return to
the system setup screen.
When the date, time and system flags have
been set correctly, press the “ABORT” key
to return to the Setup menu.
As of January 1, 2003 the standard IR-SNIF
monitor is capable of detecting and
responding
to
the
following
list
of
refrigerants.
R-11, R-12, R-13, R-22, R-113, R-114, R-
123, R-134A, R-401A, R-401B, R-402B-
HP81, R-404A-HP-62, R-407A-AC9000, R-
408A, R-409A, R-410A-AZ20, R-500, R-
502, R-503, R-507-AZ50
This list changes over time, so it is
recommended that the operator review the
1)…Change Code
2)…System Flags
3)…Alarm Test
ABORT ->
Program Time/Date
Day (Sunday = 0): 3
Enter Hr (0-23): 12
Enter Minute: 35
1)…IR Setup
2)…N/A
3)…System Setup
4)…Contact ABORT
4)…Date/Time
5)…Trending
<- ABORT
Program Time/Date
Month (1-12): 10
Day (0-31): 27
Year (00-99): 04