SENS EnerGenius® DC Compact Technical Manual
58
DC LED
1.Check that charger voltage is set
correctly for the battery. After
making any correction to the
setting, remove both AC and DC
power for 1 minute, then reapply
power.
ALTERNATING
FLASHING YELLOW
-
No output
1. Illegal
configuration
1. Ensure that charger has been
programmed to desired and
allowable settings.
SYNCHRONIZED
FLASHING YELLOW
-
No output
1. Missing terminator
2. Missing/damaged
rectifier device
1. Verify a terminator is
connected in the display board
SENSbus port.
2. If step 1 does
n’t resolve issue, a
charger failure is the likely cause.
Contact SENS or replace charger.
ALTERNATING
FLASHING RED
-
No output
1. Missing or invalid
code (boot load
required)
1. Update charger firmware using
setup utility.
2. If step 1 doesn’t resolve issue
or setup utility is not available,
replace charger
ALTERNATING
FLASHING GREEN
-
Starting-up
1. Charger is still
powering-on
2. Failed display
board
1. Remove both AC and DC power
for 1 minute and then reapply
power. Allow charger at least 1
minute to fully boot.
2. If step 1 doesn’t resolve issue, a
display board failure is the likely
cause. Replace display board.
-
-
YELLOW Filter Error
Filter Issue
1. Clean module filter as directed
in manual.
2. Ensure ventilation openings are
not obstructed.
-
-
RED
Fan Error
Fan Failure
1. Replace module fans as
directed in manual.