SENS EnerGenius® DC Compact Technical Manual
45
234
0x0EA
235
0x0EB Unit Line Current 1
AC Line 1 Current
A
32768
236
0x0EC
237 0x0ED Unit Line Voltage 2
AC Line 2 Voltage
V
32768
238
0x0EE
239
0x0EF Unit Line Current 2
AC Line 2 Current
A
32768
240
0x0F0
241
0x0F1 Unit Line Voltage 3
AC Line 3 Voltage
V
32768
242
0x0F2
243
0x0F3 Unit Line Current 3
AC Line 3 Current
A
32768
244
0x0F4
245
0x0F5 Unit State Timer
Timer for elapsed time with a given
state
Sec
1
246
0x0F6
247
0x0F7
Unit Battery Check
Due
Time until next Battery Check
Sec
1
248
0x0F8
249
0x0F9
Unit Number of
Chargers
Number of modules
Num
1
250
0x0FA
251
0x0FB
Unit Redundancy
Level
Number of redundant modules
Num
1
11.4.
Basic Charging Alarms Bit Definition
Bit Address
Name
Description
Decimal
Hex
0
0x00
AC Fail
AC input voltage is not detected by the module.
1
0x01
High DC
DC output voltage is above the High DC Voltage alarm setpoint.
2
0x02
Low DC
DC output voltage is below Low DC Voltage alarm setpoint.
3
0x03
Module Fail
Module has failed. Module is not able to provide the current
demanded by the battery and/or load or is providing more current
than the unit’s control system is commanding.
4
0x04
Over Voltage
Shutdown
DC output voltage is above Over Voltage Shutdown setpoint and unit
has executed a high voltage shutdown. This only occurs when the
overvoltage is caused by the charger.
5
0x05
Reverse
Polarity
Battery is connected backwards. Output is disabled until the condition
is corrected.
6
0x06
Unused
Unused
7
0x07
Incompatible
Battery
Unit is connected to an incompatible battery and is unable to bring up
the output voltage after a set period of time.
8
0x08
Invalid
Settings
Settings are not valid. Output is disabled until the condition is
corrected.
9
0x09
Unused
Unused
10
0x0A
Thermal Fold
Back
Output power has been reduced to protect from over-heating.
11
0x0B
Temperature
Probe Fault
Disabled or failed remote temperature sensor. Temperature
compensation is forced OFF when sensor is shorted.
12
0x0C
Current
Limiting
Charger is operating at maximum allowable output, either maximum
current or maximum power, whichever occurs first.
13
0x0D
Ground Fault
Positive
Ground fault current to the positive output terminal is above the
Ground Fault Trip sensitivity setpoint.
14
0x0E
Low Current
Output Current is under the Low Current Alarm setpoint.
15
0x0F
Load Share
Fault
Modules or chargers connected for load sharing are not sharing the
current load.
16
0x10
AutoBoost
Lockout Active
Boost mode time limit has expired and charger has returned to Float
mode. Boost mode is disabled until the time limit is reset. The Boost
time limit is reset when power is cycled.