SENS EnerGenius® DC Compact Technical Manual
22
ohm terminator in the open RJ-45 SENSbus port on the remote battery monitor to ensure a
terminator is located at both ends of the communications bus.
6.9.3.
Remote Alarm/Communications Panel Accessory Connection
—
Optional
The optional remote alarm/communications panel accessory provides the ability to adjust and
communicate with multiple chargers using one external device. The remote panel accessory may
be configured with different alarm relay assignments than the alarm relays native to the charger.
Connect a straight-thru splitter to the SENSbus RJ-45 port on each the charger and the remote
panel. Place a factory installed 120-ohm terminator in one of the positions on each splitter to
ensure a terminator is located at both ends of the communications bus. Connect a network cable
from the charger to the remote panel using another position on each splitter.
6.10.
Verify Connections
6.10.1.
Verify that all connections are secure and in the proper locations. Tighten all unused screws on
terminal blocks to secure them against vibration.
6.10.2.
Ensure all wires are routed in a way that the cover or other objects will not pinch or damage
them.