SENS EnerGenius® DC Compact Technical Manual
36
9.9.1.
Security Code Protection
Chargers may be security code protected to ensure only authorized personnel may adjust charger
settings. The default security code is 000000 meaning security code is not enabled. Change the
security code to a unique value using the front panel keypad. Contact SENS Customer Service if a
custom password is lost or forgotten (800-742-2326 or www.sens-usa.com).
9.9.2.
Menu Navigation
Use the keypad to scroll through settings to view and adjust. The keypad provides X-Y navigation
with main fields up and down and details within each field left and right (see Table 20). Press the
up and down arrow keys to scroll through main menu options. Press the left and right arrow keys
to scroll through data available within each menu. Value adjustments are made with the up and
down arrow keys. Values are saved to nonvolatile memory. Press center Enter key to return to
main fields. Press center Enter key twice to return to Home screen.
Table 20
–
Menu Navigation
Step 1
or
for main fields
Step 2
or
for details within each main field
Step 3
or
to adjust values
Step 4
to return to main fields
Step 5
to return to Home screen
9.9.3.
Menu Options
Input, output, temperature and alarm status are displayed on the front panel LCD by default.
Press the UP or DOWN arrow to access additional menus as described below. Absolute maximum
voltage limits apply to all output and alarm settings. A message is displayed indicating an
adjustment is limited due to settings conflict.
Main Menus
(Press up and
down
arrows to scroll
through Main
Menu
Options)
Configurable/Viewable
Parameters
(Press left and right arrows
to scroll through choices
within each Menu Option)
Parameter Descriptions
Latched Status
Clear Failure
Clear status of all latched alarms.
Meters
AC Input
AC input voltage and frequency
DC Output
(voltage)
DC output voltage and current
DC Output
(power)
DC output watts and % of rated output
being provided
Battery Temp.
Temperature at battery if a remote
temperature sensor is connected
Internal Temp.
Temperature inside charger
Boost Settings
Auto Boost Delay
Adjust amount of time from 0 to 5
minutes to delay before entering Boost
mode after power is cycled or battery
type is changed. Delay affects all outputs
for multiple output models.
Auto-Boost
Enable or disable Dynamic Boost mode
Auto Boost Limit
Adjust the maximum amount of time
charger will be in Dynamic Boost mode
from 1 to 100 hours. The Boost time
limit is reset if charger power is cycled or