SENS EnerGenius® DC Compact Technical Manual
14
Table 2
–
DC Output Cable Size
Charger Rated
Output Current
(Amps)
Wire Size
Resistance per
Foot
(mΩ/Ft.)
Maximum Charger to
Battery Distance (Ft.)
AWG
mm
2
120V
240V
6
14
2.5
2.5
160
320
12
4
1.6
250
500
10
6
1
400
800
8
10
0.63
635
1270
6
16
0.4
1000
2000
12
14
2.5
2.5
80
160
12
4
1.6
125
250
10
6
1
200
400
8
10
0.63
317
634
6
16
0.4
500
1000
25
14
2.5
2.5
38
76
12
4
1.6
60
120
10
6
1
96
192
8
10
0.63
152
304
6
16
0.4
240
480
35
14
2.5
2.5
NEC - not allowed
12
4
1.6
NEC - not allowed
10
6
1
69
138
8
10
0.63
109
218
6
16
0.4
171
342
4
25
0.25
274
548
2
35
0.16
429
858
50
14
2.5
2.5
NEC - not allowed
12
4
1.6
NEC - not allowed
10
6
1
48
96
8
10
0.63
76
152
6
16
0.4
120
240
4
25
0.25
192
384
2
35
0.16
300
600
The above lengths consider the resistance of the battery and cables only and do not take into
account any additional interconnects. The above lengths factor in a maximum voltage drop of 2% of
the nominal voltage. The above lengths are for operation at 25°C/77°F. For high temperature
installations (50°C/122°F) increase wire gauge by 20%.