USER MANUAL – Z-TWS4/Z-PASS2-S/S6001-RTU
195
19.1.20
SERVICE_CTRL
The SERVICE_CTRL FB enables or disables connection services, based on the
required service level.
When first called, it runs a process which starts the procedure;
on subsequent calls, it only checks if the process has finished its job.
The FB has the following input parameters:
- SERVICE_ENABLE : TRUE -> enable connection services
FALSE -> disable connection services
- SERVICE_LEVEL : this parameter defines the "Security Level", that is it tells
which connection services shall be enabled/disabled;
possible values are:
0: None
1: VPN Connection
2: VPN Service
3: Internet Connection
4: SMS Service
-1: the value of the "Security Level / Service Disable" configuration parameter
will be used
- TIMEOUT : timeout, in seconds
- @ENABLE : TRUE -> FB is executed
FALSE -> FB is skipped
The FB has the following output parameters:
- RESULT : -2, when called with ENABLE=FALSE
-1, in case of any failure
0, if the process is still running
1, if the process has successfully finished
2, if timeout has expired
- ERROR : this parameter is meaningful only when RESULT=-1; in all other cases,
it is set to 0;
possible values are:
1: the FB has been called with SERVICE_LEVEL=0
2: the procedure to enable/disable the connection services is already running
3: the CPU configuration procedure is running -> FB execution has been aborted
4: connection services are disabled since Remote Connection Disable (RCD)
digital input is HIGH -> FB execution has been aborted
Содержание S6001-RTU
Страница 35: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 35 Then import the Library menu Tools Import...
Страница 68: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 68...
Страница 76: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 76...
Страница 86: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 86...
Страница 87: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 87...
Страница 107: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 107 Once the upload is successfully completed the following page is shown...
Страница 121: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 121...
Страница 127: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 127 When the procedure is completed the following page is shown...
Страница 133: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 133...
Страница 158: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 158 Select the mbus_vars csv file and click save The variables are imported...
Страница 160: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 160 Now create the Embedded Shared Memory Insert a Master Port...
Страница 162: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 162 Select the mbus_shm csv file...
Страница 165: ...USER MANUAL Z TWS4 Z PASS2 S S6001 RTU 165...