Version : 1.09
69
Index
Name
R/W Description
17
PrgEnb
*
Program Enable: when reset to ‘0’, allows stopping the execution of
BASIC/Ladder program. It can be useful to execute the program manually (see
next).
18
PrgOnc
1
Program Once: when set to ‘1’, executes the cycle of BASIC/Ladder program
once. Useful for debugging the program.
TB
OX
LT2
resets the variable automatically.
19
TcpIpLog
*
TCP Logging: Not needed with
TB
OX
LT2
. All logs available from TWinSoft main
menu: ‘Communication’
‘Retrieve from TBox’
‘Trace Log’.
20
ALAovf
*
Alarm Overflow: overflow in the stack of alarms. The size of the stack of alarms
can be adjusted from the ‘Advanced’ properties of the RTU
21
ComErr
0
Communication error: general communication error flag. It means that one of
the communication ports (of the CPU or of a communication card) used as
‘Master’ has encountered a communication error. (SET)
22
SmtpEr
0
Smtp Error: an error occurred while sending an e-mail. (SET)
23
FtpErr
0
Ftp Error: an error occurred while sending files. (SET)
24
NTPErr
0
NTP Error: an error occurred while setting time of
TB
OX
LT2
. (SET)
25
GpsVF
-
GPS: GPS validity (connected on COM1). GPS returns a valid signal.
Validity of the signal. When changes to ‘1’, it indicates the GPS receives
sufficient signals to calculate its position (from minimum 3 satellites).
When changing from 0 to 1, the time of
TB
OX
LT2
is set to the time of GPS,
with correction in regards to GMT according to the location of TBox.
If you want to update the time manually, you reset the variable
26
GPRSErr
0
GPRS Error: an error occurred during GPRS connection.
TB
OX
LT2
does not
succeed to connect (not supported yet) (SET)
27
ModemLog
*
ModemLog: Not needed with
TB
OX
LT2
. All logs available from TWinSoft main
menu: ‘Communication’
‘Retrieve from TBox’
‘Trace Log’.
28
SystemEr
0
SystemErr: the RTU detected an error during starting. Typically a problem with
a card (not supported yet) or a discordance between cards detected in
program and cards installed (SET)
29
MmcToRTU
-
SD card: indicates whether the program has been loaded from the micro SD.
1 = the program of the micro SD is different from the one of the RTU and has
been loaded from the micro SD.
0 = there is no micro SD; the micro SD is empty; the program of the micro SD is
identical to the one of the RTU (see also appendix C. Plug&Go)
30
DigChrOv
-
Chronologies: Indicates that the amount of records in the digital chronology
has reached the maximum selected
30
DigChrOv
-
Chronologies: Indicates that the amount of records in the digital chronology
has reached the maximum selected
31
AnaChrOv
-
Chronologies: Indicates that the amount of records in the analog chronology
has reached the maximum selected
32
RsDigChr
-
Chronologies: Allows emptying the digital chronology using a SET.
Automatically reset by OS
33
RsAnaChr
-
Chronologies: Allows emptying the analog chronology using a SET.
Automatically reset by OS
34
BusError
-
Not used
35
MasterAnsw
*
ModBus Transaction: when set to 1, allows handling of ModBus Transactions
on incoming call. It concerns then only ModBus Transactions through
modem
36
DynDnsEr
0
TCPIP: error during a connection to DynDNS server. (SET)
37... 44
Tsl_Xa
-
Alarm: there are 8 time slices that can be used to build Time Tables.
Those 8 variables indicate the activity of each of them
45
DisAla2
*
Alarm: flag #2 that can be associated to any Alarm condition. When at value ‘1’,
inhibits the sending of alarm
Содержание TBOX LT2-530 Series
Страница 1: ...User s Guide Cabling Technical Specifications Version 1 09 LT2...
Страница 10: ...Version 1 09 10...
Страница 11: ...Version 1 09 11...
Страница 17: ...Version 1 09 17...
Страница 20: ...Version 1 09 20...
Страница 21: ...Version 1 09 21...
Страница 38: ...Version 1 09 38...
Страница 39: ...Version 1 09 39...
Страница 151: ...Version 1 09 151...
Страница 175: ...Version 1 09 175...