Version : 1.09
194
Example of cabling analog inputs of –LT2 through Terminal Blocks:
Using separate GND cables.
To measure temperature with PT1000,
a current of 0.1 mA is sent to the probe.
A variation of 1 °C corresponds to a variation
of the resistor of 3.8
Ω
With a current of 0.1 mA it gives
0.38 mV per °C
Using one GND cable.
The GND cable represents a little resistor,
common to temperature probes and sensors.
One meter of 0.5 mm² represents a resistance
of 0.034 Ω
Imagine a 4..20mA sensor returning 20mA.
20mA in a resistor of 0.034 Ω gives a voltage of
0.68 mV.
With a voltage of 0.38 mV per °C it constitutes
an error of almost 2°C on temperature inputs.
GOOD
BAD
0
Gnd
2
1
1
3
5
4
0
Gnd
+
-
Pt1000
0
Gnd
2
1
1
3
5
4
0
Gnd
Pt1000
+
-