External Source. All the following parameters concern the Slave station:
Device:
select an existing external device from the ‘Resources’. You can create one clicking the
button
Type:
select the type of the external variable. The choices are:
With external source ‘ModBus device’ (any
TB
OX
MS
,
TB
OX
LT,
, any ModBus device)
Types
Connection in remote device
ModBus Function
Digital input
Only digital input(s)
2
Coil
Digital output(s) or register(s)
1, 5 or 15
Analog input
Only analog input(s)
4
Holding register
Analog output(s) or register(s)
3, 6 or 16
Operations
Types
ModBus Functions Max. Quantity
(*)
Read Digital
Digital Input
2
1600 (see Warning below)
Read Digital
Coil
1
1600 (see Warning below)
Read Analog
Analog Input
4
125 (16 bits) - 62 (32 bits)
Read Analog
Holding Register
3
125 (16 bits) - 62 (32 bits)
Write Single Digital
Coil
5
1
Write Single Analog
Holding Register
6
1 (word)
Write Multiple Digital
Coil
15
800 (see Warning below)
Write Multiple Analog
Holding Register
16
100 (16 bits) - 50 (32 bits)
(*): Maximum quantities for
TB
OX
LT2
,
TB
OX
LITE
,
TB
OX
MS
. You also have to check the maximum quantities of the
‘Remote device’-they could be less.
With External source ‘Remote TBox’ (
TB
OX
CPU-3
)
Description
Operations
Tag types
Max. Quantity
Digital I/O
Read/Write
IOD, T4m
16
Analog I/O
Read/Write
IOW, I4M
8
Digital registers
Read/Write
DIR, STD
1600 (see Warning below)
Analog registers (8 bits)
Read/Write
STB
8
Analog registers (16 bits)
Read/Write
AIR, STO
100
Analog registers (32 bits)
Read/Write
TOT
8
Analog registers (32 bits)
Read/Write
FLT
8
Timers
Read/Write
ATP, ATV, DTI
16
Counters
Read/Write
ACP, ACV, DCN
16
Special Registers
Read/Write
DSPE, ASPE
16
Register ‘Sampling Table’
Read/Write
ECH
16
(*): with quantity > 16, ModBus addresses and quantities must be multiple of 8
When accessing digital variables (DIV, DIR, …) into
TB
OX
CPU-3
, make sure you use
multiples of 8 for: quantity and address of Variable in External Source
Address :
The ModBus address must be typed according to the indication of the user’s guide of the
Remote device. Communicating to a
TB
OX
, you have to refer to the TWinSoft application
and its configuration of Tags.
Содержание TBOX LT2-530 Series
Страница 1: ...User s Guide Cabling Technical Specifications Version 1 09 LT2...
Страница 10: ...Version 1 09 10...
Страница 11: ...Version 1 09 11...
Страница 17: ...Version 1 09 17...
Страница 20: ...Version 1 09 20...
Страница 21: ...Version 1 09 21...
Страница 38: ...Version 1 09 38...
Страница 39: ...Version 1 09 39...
Страница 151: ...Version 1 09 151...
Страница 175: ...Version 1 09 175...