myGrid
Installation Notes
Installing the Batteries
Warning: Batteries are very dangerous. Battery fault currents are 1,000s of amps. Please read
and adhere to the safety information provided with the batteries.
Safe practices when working with battery systems
–
Remove all conductive jewellery or watches before working on batteries.
Keep any conductive tools well clear of the batteries
Only use non-conductive or insulated tools when working on or near the batteries.
Double check the connection orientation of the batteries and battery links.
Before connecting any links between battery terminals, check the voltage between
those battery terminals to be zero using a volt meter.
Care MUST be taken when connecting the battery interlinks. Please note that the
lose end of the battery interlink is live and must be prevented from shorting to
other batteries or battery terminals.
NOTE: Ensure Main Battery and Pre-charge/Battery Sense circuit breakers are in the O / Off
position before making any connections to the batteries.
B
ATTERY
T
ERMINAL
S
IZE
The battery positive terminal is larger than the battery negative terminal. It is important to
ensure that only a RED coloured clamp is fitted to a battery positive terminal and the BLACK
smaller clamp is fitted to a battery negative terminal.
B
ATTERY
I
NTERCONNECTS
The supplied battery interconnects have been pre-assembled, tightened and designed to suit
the battery configurations pictured below. There is no need to loosen any of the pre-assembled
battery interconnects. Adjust the position of the batteries by sliding them to fit rather than
adjusting the battery interconnects.
Battery Link
Used for connecting two batteries in series
–
battery positive to battery negative.