myGrid 120 VDC 40kWh Battery Connections
Warning: Ensure Main Battery and Precharge Circuit breakers are 0 / Off position.
NOTE: Battery fault currents are 3,970 amps
20 x 330 Ah 6 VDC blocks in series combination
Right Hand Frames
–
One 24 VDC group made up of four series 6 VDC batteries.
Left Hand Frames
–
Two groups of 12 VDC made up of two series 6 VDC batteries.
Battery Sense +ve (Brown)
Battery Sense -ve (White)
Battery Sense Mid (Yellow)