Non-verified alarm
•
Verified alarm
Any of these alarm inputs activating when the panel is not already in alarm causes the
following:
•
Buzzer sounds steady.
•
Cancels active fire drill.
•
Common Alarm LED turns ON.
•
Individual zone LED (if programmed) turns ON.
•
Common Alarm relay does not activate.
•
PAS timer starts for 15 seconds.
•
All outputs programmed to the input are not activated.
When the PAS alarm has been acknowledged by pressing the Alarm Acknowledge button
within 15 seconds, the following sequence occurs:
•
Buzzer silences
•
Common Alarm LED remains ON.
•
Individual zone LED (if programmed) remains ON.
•
PAS timer starts for 180 seconds (3 minutes). This is the time allotted to reset the
system and avoid any true alarm sequence.
When the PAS alarm has been acknowledged within the given time limits and the system
resets, the following occurs:
•
The buzzer remains silenced.
•
Common Alarm LED turns OFF.
•
Individual zone LED (if programmed) turns OFF.
•
Cancels the alarm event with no log reference.
•
Fire alarm system returns to normal.
If at any time during the Positive Alarm Sequence a second alarm (PAS or otherwise) is
actuated or the given time limits expire, the fire alarm will go into evacuation mode and the
following occurs:
•
Common Alarm relay activates if Aux disconnect is not active.
•
The Auto Signal Silence timer activates (if configured).
•
The Signal Silence Inhibit timer activates (if configured).
•
If Aux disconnect is not active, activates all non-disconnected indicating circuits
programmed to the input.
•
Activates non-disconnected strobes associated with the input.
•
Activates non-disconnected signals associated with the input at the evacuation rate.
In a pre-configured FACP the Positive Alarm Sequence may be enabled or disabled as the
user requires. For more information on enabling or disabling the Positive Alarm Sequence see
5.7.1 Enabling or Disabling the Positive Alarm Sequence.