Auxiliary Supply (supervised, regulated)
Supervised auxiliary power is used to power the remote annunciators and smart relay
modules.
This filtered circuit is supervised for shorts.
A short will:
•
Disconnect the power until the “RESET” button is pressed.
•
Generate a trouble signal
The circuit must be supervised for opens utilizing the End of Line Relay Model EOLR-1A as
shown in Figure 22. This supply is rated at 24VDC regulated/500mA max/1V voltage drop
maximum.
Unfiltered Supply (unsupervised, unregulated)
This unregulated supply is not supervised. When supervision is required, the circuit must be
supervised for opens utilizing the (UL listed - S3403) End of Line Relay Model EOLR-1A. This
supply is rated at 24V FWR/1.7A max. If there is a short on this circuit, the auxiliary power
does not recover automatically when the short is removed. The main power and the battery
must be disconnected, then reconnected and the panel reset to re-establish the auxiliary
power supply.
Figure 22 Supervision of Auxiliary Supplies
1
4
2
3
5
6
DETECTOR POWER SUPPLY
22VDC, 200mA
MAX. CURRENT - 300mA
MAX. RIPPLE VOL. 5mV
(POWER LIMITED)
END OF LINE RELAY
+
-
RESETTABLE
AUXILIARY
POWER
OR
AUXILIARY
SUPPLY
OR
UNFILTERED
SUPPLY
FIRE ALARM MAIN BOARD
E.O.L.
47K Ohms
ION SMOKE
DETECTOR
PHOTO SMOKE
DETECTOR
HEAT DETECTOR
+
-
+
-
B
LEGEND
Class B (Style B)
WIRING
Loop
A
MIX-101P
Violet
White
Red
Black
Red
Black
Supervision for Auxiliary Supplies
MINI MONITOR
MODULE
AUX 2
Connect auxiliary devices here*
* Use this supervision set-up only
if auxiliary devices are used.