5.2.1 Alarm Input (Non-Verified)
An un-bypassed, non-verified alarm input entering into alarm activates the common alarm
sequence.
Common Alarm Sequence
•
Updates un-bypassed relay, signal, and strobe outputs based upon their configuration.
•
Activates Alarm zone status indicators associated with the input.
•
Alarm input activations display first and as the highest priority on the shared display in
the common queue.
•
Devices configured as alarm inputs display a pre-alarm condition on the shared display
and on the alarm zone status indicator.
•
Restoring the pre-alarm condition clears the status. If the input goes from pre-alarm to
alarm, the pre-alarm status will be replaced with the alarm status for the input.
•
Devices configured as alarm inputs display an alarm condition on the shared display
and on the alarm zone status indicator.
•
Once an alarm input is in alarm the alarm condition is latched until system reset
(changes in status from alarm to pre-alarm or to normal are ignored).
5.2.2 Supervisory Inputs
Devices can be configured as latching or non-latching supervisory inputs. Any un-bypassed
supervisory input entering alarm activates the common supervisory sequence.
Common Supervisory Sequence
•
Updates un-bypassed relay, signal, and strobe outputs based upon their configuration.
•
Activates Supervisory zone status indicators associated with the input.
•
Supervisory input activations display as the second highest priority on the shared
display in the common queue.
Auxiliary Disconnect
Aux Disc
5.2.7
X
Buzzer Silence
Buzz Sil
5.2.7
X
Signal Silence
Signal Silence
5.2.7
X
Acknowledge General
Alarm
Ack GA
5.2.7
X
Audible Walktest
Audible Walktest
5.2.8
X
Silent Test
Silent Test
5.2.9
X
Manual Day/Night
Manual Day/Night
X
Auto Day/Night
Auto Day/Night
X
Auxiliary Reset
Auxiliary Reset
5.2.7
X
Verified Alarm
Verified Alm
5.2.12
X
Table 12 Configurable Input Types (Continued)
Input Type
As listed in
Configurator
Description
located in
Section number
Device Types
Detectors
Dual Mini Modules
Zone Module
Mini Monitor Module
Monitor Module