29
5.7.1 Enabling or Disabling the Positive Alarm Sequence
Enabling or Disabling the Positive Alarm Sequence is done using the numeric keypad. For
more information on how to use the Numeric Keypad see section 6.2.1 Numeric Keypad and
Cursor Buttons on page 46. For details on configuring the FACP for PAS see LT-1148SMOD
MR-3318 Programming Manual.
How to Enable or disable the Positive Alarm Sequence
1. From the Keypad of the FACP press
M
to enter the
Menu
.
2. Using
the
Up and Down
cursor buttons, scroll to
Operation
.
3. Press
Enter.
4. In
the
Operation Menu
scroll to
Positive Alarm
.
5. Press
Enter
.
6. You will now see the current status of the
Positive Alarm Sequence
and will be
prompted to change status.
Figure 7 Enabling the Positive Alarm Sequence
7. To change the status press
Enter
.
8. To exit without changing the status press
Cancel
.
5.8 Remote Annunciator Operation
The MR-3318 System supports the following types of annunciators
•
RAX-LCD-LITE shared display annunciator.
•
RAM-3318-LCD shared display annunciator.
•
Conventional LED/switch annunciators.
Both types of annunciators are connected to the panel via the RS-485 serial link.
The maximum number of annunciators is seven (7). Configuration of the annunciators is done
via the MSW-042 software configurator.
Note:
There will be no notification message advising a change of status.
Pos Alarm disabled
Enable? Y
i