51
7.0
Wiring
This chapter describes the proper field wiring for the MR-3318.
7.1 Wiring Tables
7.1.1 Addressable Loop Wiring Maximums
Advanced Protocol and CLIP Devices
•
Maximum Loop Current = 350 mA
•
Maximum Loop Resistance = 40 ohms
•
Maximum Loop Capacitance = 0.5
μ
F
•
Maximum Number of Isolators = 20
7.1.2 RS-485 Wiring to Annunciators and other Devices
•
Use twisted shielded pair
•
22 AWG maximum of 2000 feet
•
20 AWG maximum of 4000 feet
7.1.3 NAC and Auxiliary Power Supply Circuits
Table 18 Advanced Protocol and CLIP Devices Addressable Loop Wiring Table
Wire Gauge
Maximum Wiring Run to Last Device
(AWG)
ft
m
18
3030
923
16
4760
1450
14
7690
2343
12
9820
2993
Table 19 NAC and Auxiliary Power Circuits Wiring Table
TOTAL
SIGNAL
LOAD
MAXIMUM WIRING RUN TO LAST DEVICE (ELR)
MAX. LOOP
RESISTANCE
18AWG
16AWG
14AWG
12AWG
Amperes
ft
m
ft
m
ft
m
ft
m
Ohms
0.06
2350
716
3750
1143
6000
1829
8500
2591
30
0.12
1180
360
1850
567
3000
915
4250
1296
15
0.30
470
143
750
229
1200
366
1900
579
6
0.60
235
71
375
114
600
183
850
259
3
0.90
156
47
250
76
400
122
570
174
2
1.20
118
36
185
56
300
91
425
129
1.5
1.50
94
29
150
46
240
73
343
105
1.2
Notes:
Main Board NAC Circuits are rated for of 1.5 Amperes each.
Maximum Voltage Drop Should Not Exceed 1.67 Volts
i