Zone indicators, including the Smart Relay Module (MR-2312-SR(W)12) function
normally during the test, displaying the input status when it is activated.
•
Other Relays and signal correlations to input circuits are not processed during walk-test.
Correlations to system status will still be processed.
•
All common controls and keys not explicitly required for the walk-test operation are
disabled while the walk-test is active.
•
The alarm verification and waterflow retard operation is disabled on inputs during walk-
test.
During an Audible walk test:
•
activating any input activates all signals for half a second.
•
Trouble on any input activates all signals continuously for 5 seconds. After the code is
transmitted, the input resets (if resettable) and is tested again. If it is still in alarm or
trouble the code will be re-transmitted.
Use the
UP
and
DOWN
cursor keys to scroll to the desired option press the
Enter
button.
The following message will show the walk test initializing.
While the walk-test is active the following message is displayed on the screen:
where nnn and mmm are continuously updated counts of the number of alarms and troubles
which have been recorded during the test (alarms includes all input circuit types tested).
Selective Output Testing
Walk Test can be operated with only a selection (up to 64) of outputs. To do this, select audible
test. The next screen will be:
Select “No” by using the right arrow key and the next screen will say:
Select Test Type
1. Audible Test
2. Silent Test
Initializing
Walk test ...
--Walk test Active --
Alarm :nnn Trbs :mmm