25
Additional Operation Features
•
When using CLIP devices once the FACP activates the sensor LED, an attached Relay/
Sounder base and any Remote Devices wired to the base are also activated.
Suppressing the device LED via the NF flag in the configurator means the Relay/
Sounder base and any Remote devices wired to the base will not activate.
•
When using AP devices the FACP activates the sensor LED and the Remote Device
output separately. Suppressing the device LED via the NF flag in the configurator still
allows the activation of any remote device wired to the base. The AP protocol does not
support Relay/Sounder Bases at this time+.
•
The panel can synchronize strobes directly without the use of the synchronous module.
•
Depending on the device, the system can detect open and short troubles and report it as
an output circuit trouble.
5.3.1 Signal Output
For audible devices such as bells and piezo mini-horns. Signals operate in alert (two stage)
and/or evacuation rate.
5.3.2 Strobe Type Settings
Normal (non-synchronized)
•
Strobe circuits operate similar to signals except that they are always turned ON
continuously (they are not affected by the alert or evacuation rates) if configured as
Normal.
•
Configuring strobes as Normal does not use a sync protocol for the output circuit.
•
Silenceable or non-silenceable.
Synchronized
Output circuits can be configured with various synchronization protocols.
When the output circuit is configured as strobe and also configured as non-silenceable and the
device used on the output is a combination of horn and strobe, then if the signal silence is
activated while the circuit is active the horn(s) are silenced while the strobe keeps on flashing.
Synchronized strobes and strobe/horn models of the following manufacturers are supported:
System Sensor, Wheelock, Secutron, and Mircom.
Table 13 Configurable Output Types
Output Type
As listed in
Configurator
Description
located in
Section number
Device Types
Relay Output
Module
Supv Output
Module
Relay
Relay
5.3.3
X
X
Signal
Signal
5.3.1
X
X
Strobe
Strobe
5.3.2
X
X
Note:
Silencing of the horn depends on the feature provided by the manufacturer of the
horn/strobe combination. Some models of the horn/strobe combination may not
have this feature and will not work as described above.
i