1. SPECIFICATIONS

2. PRELIMINARY INSTALL GUIDE

3. COMPONENTS LIST

4.0 INBUILT AGAINST COMBUSTIBLE WALL

5. INBUILT INTO ISLAND WALL 

NON COMBUSTIBLE SURROUNDINGS

6. FREE STANDING INSTALL

7. OPERATION & MAINTENANCE

8. TEST RESULT

9. WARRANTY

SEGUIN

NOTICE TO INSTALLER: 

These instructions must be left with the owner, who should keep them for future use.

4.1 MASONRY BRICK INSTALLATION 
4.2 HEBEL INSTALLATION 
4.3 SKAMOL: REFER TO SKAMOTEC 225 MANUAL

Multivision Hydro 80 

INSTALLATION & USER GUIDE

Содержание SEGUIN MULTIVISION HYDRO 80

Страница 1: ...TIBLE SURROUNDINGS 6 FREE STANDING INSTALL 7 OPERATION MAINTENANCE 8 TEST RESULT 9 WARRANTY SEGUIN NOTICE TO INSTALLER These instructions must be left with the owner who should keep them for future use 4 1 MASONRY BRICK INSTALLATION 4 2 HEBEL INSTALLATION 4 3 SKAMOL REFER TO SKAMOTEC 225 MANUAL Multivision Hydro 80 INSTALLATION USER GUIDE ...

Страница 2: ...2 COMPLIANCE PLATE AND SERIAL NUMBER The instructions in this manual are recommendations only the distributor and manufacturer bears no liability to the interpretation of these instructions ...

Страница 3: ...ecommended that this fireplace be installed by a qualified and licensed trades professional You will find in this guide the answers to most of your questions should you require further assistance we recommend you contact your retailer Before igniting your fireplace for the first time please carefully read this manual Follow sculptfireplacecollection on Instagram SculptFireplaceCollection on Facebo...

Страница 4: ... we reserve the right to alter specifications without notice All units comply and MUST be installed to Australian New Zealand Standard AS NZS 2918 2018 When in use some parts may become hot A suitable fire guard is recommended where very young elderly or infirm are concerned ALL FIREPLACES IN THIS MANUAL CONFORM TO AUSTRALIAN AND NEW ZEALAND STANDARDS AS NZS 2918 2018 DOMESTIC SOLID FUEL BURNING A...

Страница 5: ...Pa 665mm 1185mm 800mm 250mm 451mm Thermal power Facade Glass door Minimum flue height Flue sizes Includes hot air kit Outside air kit Warranty Hearth dimensions Nominal 25 9kW Water System 14 3kW Clean frameless design no trim Secure swing door 4 6m 250mm active 300mm 350mm A duct and register Recommended for well insulated homes 10 year firebox warranty Minimum 500mm in front of any part of firep...

Страница 6: ...m Before any work is carried out as per local and national regulations and laws this appliance MUST be installed by a licensed professional as per Australian and New Zealand Standards 2918 2018 IMPORTANT WARNING It is strictly forbidden to use any combustible materials ie wooden framing plaster etc near or around this appliance Any exception from this rule is a health and safety hazard which will ...

Страница 7: ...ndently The order of steps listed in this manual are recommendation only It is strongly recommended that the licensed trade professional who is performing the installation of this appliance completely read and comprehend all instructions in this manual prior to proceeding Sculpt Fireplaces Seguin reserves the right to change these specifications without prior notice PLEASE READ PRIOR TO INSTALL Fo...

Страница 8: ...t fireplace Collection All images and diagrams in this manual are for installation reference purposes only and are not to scale The distributor and manufacturer bears no accuracy of these images and accepts no liability The purpose of these images and diagrams is to act as a guide in conjunction with the written components and are NOT to instruct independently The order of these steps are a recomm...

Страница 9: ...bustion air inlet must be a minimum 300cm2 and ideally positioned see point A B on diagram Airways must be clear and checked regularly to ensure air circulation is correct otherwise it may cause over heating PLEASE READ PRIOR TO INSTALL Clearance Gap 50mm Firebox Non combustible wall Hot air grid Air vents False Ceiling A B 2 PRELIMINARY INSTALL GUIDE ...

Страница 10: ...materials Make sure that there is a distance approx 5 cm between the insert and the thermal insulation of the casing By ensuring proper ventilation i e free flow of convection air from the air inlet to the grid outlet the fireplace will have enough air to cool down the insert While placing the insert make sure that the base on which the insert rests does not block the flow of convection air Given ...

Страница 11: ...ion of the system and protect the water jacket against damage due to inadequate water level IMPORTANT You must not establish a fire in the fireplace insert before filling up the water jacket with water Otherwise any damage resulting from use against the recommendations of the manufacturer will void the product guarantee The insert casing must provide access to the hydraulic fittings of the water j...

Страница 12: ...responsible for all connections IMPORTANT Water must be present and flowing through the system if the firebox is to be used 2 PRELIMINARY INSTALL GUIDE INSTALLATION INSTRUCTIONS OF MULTIVISION 8000 THERMOSTAT DIAGRAM FOR THE INSTALLATION OF THE MULTIVISION 8000 THERMO COMBINED WITH A BOILER ...

Страница 13: ...lve to the expansion vessel to protect the same against overheating since the water temperature may occasionally exceed 95O C to the detriment of the piping e g made of plastic The intake pipe diameter should be or All pipes mounted in unheated rooms as well as the expansion vessel should be insulated to protect them against freezing and or damage to the water jacket INSTALLATION INSTRUCTIONS OF M...

Страница 14: ...valve and thermostatic valve on the coil The installation of the cooiling coil is essential for the correct operation of the appliance IMPORTANT Installation of the equipment in a closed system in buildings which are equipped with their own water supply systems water wells is not recommended since in the event of a power cut the system does not provide water necessary to collect excess heat from t...

Страница 15: ... release which helps you increase or decrease the amount of flue gas removed The chimney damper is a movable part installed inside the flue pipe through which flue gas is removed The damper is controlled manually using a lever that is located on the right side of the front panel where the insert model contains multiple sides the lever is located on the side of the door While establishing the first...

Страница 16: ...SS FLUE 250MM DIAMETER ACTIVE 900MM GALVANISED FLUE 300MM DIAMETER INSULATING OUTER 900MM GALVANISED FLUE 350MM DIAMETER INSULATING OUTER WIND RIM COWL TO SUIT 5 4 4 1 COMPONENTS QUANTITY 4 5M INBUILT TRIPLE SKIN FLUE KIT SEGUIN MULTIVISION HYDRO 80 900MM STAINLESS FLUE 250MM DIAMETER ACTIVE 900MM GALVANISED FLUE 300MM DIAMETER INSULATING OUTER WIND RIM OPTION B COWL TO SUIT 5 1 Double skin black ...

Страница 17: ...ap behind the firebox Refer to Step 5 Outdoor Air Kit STEP 2 BACK WALL Using masonry brick construct the back wall from the base to the top of the ceiling STEP 3 SHEET METAL LAYER OPTIONAL STEP Place a thin piece of sheet metal on top of the bricks in order to level the base and safely manoeuvre the firebox Allow a minimum of 100mm on all sides if possible All images from page 17 35 are for illust...

Страница 18: ...the fireplace is located can result in emanation of smoke to flow back into the room and for the unit to run inefficiently It is highly recommended that an Outdoor Air Kit be installed in 6 star or more rated homes or any install where a mechanical device ie fan takes air from the fireplace cavity transfers it STEP 6 FIRST LENGTH OF FLUE Place the first single skin length of flue with no crimp end...

Страница 19: ...ighly recommended that it is installed if not installed it will have no implication on the functioning of the unit Cut a hole in the lid of the enclosure nearest to the room where the heat is to be transferred Run the ducting from this hole into the roof space and locate to the room cut out the plaster and install a metal register into the ceiling of the next room PLEASE NOTE A maximum duct run of...

Страница 20: ...e skin flue The flue must extend a minimum 1m above the roof line and have a 3m diameter clearance from the top of the cowl to any objects in a horizontal direction IMPORTANT The flue should not include more than two 45 degree bends The angle of these bends cannot exceed more than 45 and can have no more than one length of 900mm flue between them STEP 10 FLUE INSTALLATION Triple skin flue is to th...

Страница 21: ...ckness of 75mm 4 1 MASONRY BRICK INSTALLATION STEP 14 BAFFLE PLATE The baffle plate is a rectangular element with two resting points at the back Lift the baffle plate vertically in to the combustion chamber then lower the baffle plate horizontally until the resting points is placed in to the supports at the back of the combustion chamber The two supports in the chamber should tilt the baffle plate...

Страница 22: ...TEEL FRAME Place a steel frame minimum 51mm thick on either side of the enclosure Remember to leave a 25mm air gap on the sides of the appliance IMPORTANT It is strongly recommended that the steel frame allows for a distance of 300mm to the ceiling this allows the cavity lid to be placed directly above and stop heat from traveling above the lid via the frame STEP 1 BASE Lay a masonry base minimum ...

Страница 23: ... requirements as specified above For custom made vents please contact your nearest dealer ALL VENTS MUST NOT BE PLASTIC OR COMBUSTIBLE Using Hebel build a layer of bricks from the base to the top of the ceiling on either side of the enclosure STEP 5 BACK WALL COMPLETION For structural support place a steel frame on the back wall in front of the Hebel and connect to the two opposing steel frames ST...

Страница 24: ...ecork to seal any air gaps Before installing the remaining lengths of flue please go to the next step 15 300mm BELOW CEILING CAVITY LID TO BE FULLY SEALED TO ALL EDGES STEP 10 CAVITY LID IMPORTANT SIDE VENTS It is highly recommended the cavity lid be installed flat to ensure sufficient air flow around the appliance FRONT VENTS It is highly recommended the cavity lid be installed on an angle of 15 ...

Страница 25: ...um inner core aluminium outer poly insulated minimum RI 0 and tested to AS 4254 1 2012 Outlet MUST be metal This unit has been supplied with a ducting kit consisting of one duct and one metal register while it is highly recommended that it is installed if not installed it will have no implication on the functioning of the unit Cut a hole in the lid of the enclosure nearest to the room where the he...

Страница 26: ...T FINAL LAYER Place a layer of 12mm minimum thick heat resistant material on the exterior and finish IMPORTANT Do not use Fyrchek to finish the cavity exterior STEP 16 HEARTH FLOOR PROTECTOR The hearth must be constructed from masonry or a non combustible material and must extend a minimum of 500mm in front of the appliance 250mm on either side of the appliance and a thickness of 75mm ...

Страница 27: ...sting points at the back Lift the baffle plate vertically in to the combustion chamber then lower the baffle plate horizontally until the resting points is placed in to the supports at the back of the combustion chamber The two supports in the chamber should tilt the baffle plate downwards towards you ...

Страница 28: ... full service temperature limit and the low thermal conductivity provides maximum insulation throughout the temperature range making it the ideal product when building custom fireplace enclosures PLEASE REFER TO SKAMOTEC 225 INSTALLATION MANUAL ONLINE VIDEO SKAMOTEC 225 BUILDING BOARD FOR FIREPLACE ENCLOSURES VISIT YOUTUBE COM PLEASE NOTE THAT A SKAMOTEC ENCLOSURE CAVITY IS NOT CONSIDERED A MASONR...

Страница 29: ...base this will level the base and enable you to safely manoeuvre the firebox Allow a minimum of 100mm on all sides if possible STEP 3 SIDE FRAMES Place a steel frame minimum 51mm thick on either side of the enclosure Remember to leave a 25mm air gap on the sides of the appliance IMPORTANT It is strongly recommended that the steel frame allows for a distance of 300mm to the ceiling this allows the ...

Страница 30: ...he frame STEP 6 SIDE WALLS SECOND LAYER VENTILATION IMPORTANT Ventilation is required on the enclosure to help with air circulation A minimum of two air intake grills are required at the bottom and a minimum of two air out take grills are required on top of the masonry enclosure 2X inflow 2X outflow All vents can be positioned on either side OR the front of the masonry enclosure ALL vents must adh...

Страница 31: ...manufactured into the bottom length of the flue 15 300mm BELOW CEILING CAVITY LID TO BE FULLY SEALED TO ALL EDGES STEP 8 CAVITY LID IMPORTANT SIDE VENTS It is highly recommended the cavity lid be installed flat to ensure sufficient air flow around the appliance if 2 vents are used FRONT VENTS It is highly recommended the cavity lid be installed on an angle of 15 facing the front of the fireplace t...

Страница 32: ...TEP 12 FRONT FRAME Place a steel frame minimum 51mm thick on the front of the enclosure ensuring a minimum 25mm clearance to the unit itself STEP 11 DUCTING The duct MUST be 4 Zero type aluminium inner core aluminium outer poly insulated minimum RI 0 and tested to AS 4254 1 2012 Outlet MUST be metal This unit has been supplied with a ducting kit consisting of one duct and one metal register while ...

Страница 33: ...t the back Lift the baffle plate vertically in to the combustion chamber then lower the baffle plate horizontally until the resting points is placed in to the supports at the back of the combustion chamber The two supports in the chamber should tilt the baffle STEP 14 HEARTH FLOOR PROTECTOR The hearth must be constructed from masonry or a non combustible material and must extend a minimum 500mm in...

Страница 34: ...lack of fresh air within the room where the fireplace is located can cause emanation of smoke to flow back into the room and the unit to run inefficiently It is highly recommended that an Outdoor Air Kit be installed in six or more star rated homes or any install where a mechanical device ie fan takes air from the fireplace cavity transfers it STEP 4 INSTALLING FREE STANDING FLUE SYSTEM The first ...

Страница 35: ... towards you STEP 5 FLUE INSTALLATION The triple skin flue will then be continued into the roof cavity and above the roof line as per Australian New Zealand Standard AS NZ 2918 2018 There must be a 25mm clearance around the outer triple skin flue The flue must extend a minimum 1m above the roof line and have a 3m diameter clearance from the top of the cowl to any objects in a horizontal direction ...

Страница 36: ...es provided this will avoid any marking on the paint surface prior to it being cured The paint will polymerise after several fires Do not scrub or clean the fireplace with any rough surface such as a sponge In the case of accidental scratches make several fires until the paint is cured at which time you can delicately clean the outside of the appliance with a hot sponge Do not scratch or rub the f...

Страница 37: ...This is only a temporary condition However make sure that windows doors should be open to provide adequate ventilation While establishing the first fire it is absolutely necessary to check the functioning of the automatic water supply system at the overflow tank and in the circulation pump Please note Before building a big fire establish several fires The curing process is necessary to ensure that...

Страница 38: ...of time When the wood is piled more compact it will burn slower because the oxygen wont reach all the logs at the same time This piling is recommended if you want to heat over a longer period of time RECOMMENDED FUEL This fireplace is designed for only wood fuel Any fuel other than wood is strictly forbidden As a general rule it is recommended use dry well seasoned HARD WOOD with a 15 moisture con...

Страница 39: ...temperatures above 100 Uninitiated persons young children and infants should be monitored at all times while in the vicinity of the appliance SLOW BURNING Please be aware that this method may cause unburnt matter to accumulate in the flue system This may in the long term cause a chimney fire Our recommendation is to therefore avoid closing the damper and primary air for an extended length of time ...

Страница 40: ...clogging of the fire grate Use the cold handle supplied and pull the ash pan from the appliance You will find some ashes catching in the cavities between the ribs of the fireplate This bed of ashes caught between the fireplate is essential as it will create a more effective start up operation of the fire FORBIDDEN FUELS This appliance is not designed for burning the following fuels Solid mineral f...

Страница 41: ...e or clear ventilation shaft 6 Call authorised specialist 1 Fireplace door open 2 Too strong draught in chimney Parts subjected to normal wear and tear need to be replaced not covered by warranty see warranty terms and conditions 1 Close door 2 Install draught regulator Use special cleaning agent or clean ash from fireplace If inadequate draught see other troubleshooting suggestions Buy new spares...

Страница 42: ... entail any liability of the seller towards the buyer Full operational capacity of the device depends on the manner and intensity of use and maintenance It means that intensive use may reduce the life of all movable parts below the seller s liability period of 24 months The life of new movable parts will also depend on the manner and intensity of use and maintenance The insert is coated with a hea...

Страница 43: ...014 on the 2nd of November 2015 The appliance produced a maximum Heat output of 25 9kW Exemption from testing the Multivision 8000 solid fuel appliance should be claimed under section 1 2 3 b of AS NZS4013 2014 as the maximum heat output from combustion is greater than 25kW when fired at the prescribed high burn rate and that the appliance is intended for space heating by means of transferring hea...

Страница 44: ...utor are by no means responsible for any indirect damage originating from a handling accident 8 Cost of removal of a defective heater or re installation of a replacement heater is not covered 9 All warranties are void if the unit is outside and exposed to the elements PERFORMANCE The performance of our fireplaces are given as an indication and comparison after testing under optimum conditions Thes...

Страница 45: ...ery effort is taken to avoid errors SCULPT FIREPLACE COLLECTION cannot accept responsibility for the accuracy of any statement extract or information contained within this manual nor can any of its contributors who have submitted material for inclusion SCULPT FIREPLACE COLLECTION may change or update this manual and anything described in it without notice We will endeavour to ensure that informati...

Страница 46: ...er of Seguin Axis and Bordelet fireplaces with exclusive distribution rights throughout Australia and New Zealand Our wood fire manufacturers integrate innovation technology environmental impact operational expertise and quality whilst holding design at the forefront We aim to fill homes with the maximum of comfort while capturing the true art and meaning of a sculptural fireplace in any living sp...

Страница 47: ...47 1300 851 304 info sculptfireplaces com au PO Box 1232 Mornington VIC 3931 Edition 01 01 19 ...

Отзывы: