Date Code 20010731
Firmware Upgrade Instructions
B-5
SEL-352-1, -2 Instruction Manual
(To change the calibration settings, you will need to first enter the calibration access
level by typing
CAL <ENTER>
, and the password
CLARKE
<ENTER>
.)
15. Execute the Status (
STA)
command to verify that all relay self-test parameters are
within tolerance.
16. Apply current and voltage signals to the relay. Issue the
MET
command and verify that
the current and voltage signals are correct. Issue the Trigger (
TRI)
and Event (
EVE)
commands. Verify that the current and voltage signals are correct in the event report.
The relay is now ready for your commissioning procedure.