Component Functions
EN-US · 30.30.01.02237 · 00 · 04/20
75 / 94
Offset parame-
ter
10206 (0x27DE)
10208 (0x27E0)
Description
Request: Error Code
Response: Error Code
Index
—
Data type
bool
uint8
Length
1 bytes
1 bytes
Access
Read only
Value range
0 = No error in the connection to the
IO-Link master
1 = Timeout during establishing the
connection to the IO-Link master
Error code in accordance with the IO-
Link interface specification
Default value
—
Unit
—
EEPROM
no
Offset parame-
ter
10209 (0x27E1)
Description
Response: Additional Error Code
Index
—
Data type
uint8
Length
1 bytes
Access
Read only
Value range
Additional error code in accordance with the IO-Link interface specifi-
cation
Default value
—
Unit
—
EEPROM
no
EtherNetIP:
To access the ISDU parameters of an IO-Link device connected to the IO-Link master, an object, an in-
stance and an attribute must be specified in the object-based “Common Industrial Protocol” (CIP). The ob-
ject 0x10B must be selected for this purpose. The instance represents the IO-Link index number. The at-
tribute represents the IO-Link subindex number. Refer to the IO-Link device description for the index and
subindex. The service code is used to select the IO-Link master and port on which the service is to be exe-
cuted.
The service codes are assigned as follows:
Master # Port #
Service code
Master 1 Port 1
0x11
Master 1 Port 2
0x12
Master 1 Port 3
0x13
Master 1 Port 4
0x14
Master 2 Port 1
0x21
Master 2 Port 2
0x22
Master 2 Port 3
0x23
Master 2 Port 4
0x24