Component Functions
46 / 94
EN-US · 30.30.01.02237 · 00 · 04/20
The vacuum connections of all of the ejectors must be ventilated to the atmospheric pressure before a
zero-point adjustment can be made to the sensors.
The “0xA5” system command is used to calibrate the sensors of all of the ejectors.
A zero offset is only possible in the range of ± 3% from the end value of the measurement
range.
If the permitted limit of ± 3% is exceeded, this is reported for each ejector via parameter 0x0082.
Reset Counters
The system command “0xA7” is used to delete the two erasable counters in each ejector.
Reset Maximum and Minimum Values for Supply Voltage
The “0xA8” system command is used to delete the minimum and maximum values of the two supply volt-
ages for the sensor and actuator.
6.2.2 Device Identification
The Compact terminal SCTSi provides a range of identification data that can be used to uniquely identify
a specific device. All of these parameters are ASCII character strings that adapt their length to the relevant
content.
The following parameters can be called up:
•
Device vendor name and web address
•
Vendor text
•
Product name and product text
•
Serial number
•
Version status of the hardware and firmware (hardware revision)
•
Unique device ID and device properties
•
Article number and development status (article number, article revision)
•
Production date
•
System configuration
•
Device ID
•
Equipment identification
•
Web link for NFC app and device description file (GSD web link, NFC web link)
Offset parame-
ter
16 (0x0010)
17 (0x0011)
18 (0x0012)
Description
Device vendor name
Vendor text
Product name
Index
-
-
-
Data type
char
Length
32 bytes
Access
Read only
Value range
-
Default value
-
Unit
-
EEPROM
Yes