4.2. Flex vent manifold assembly
For qualified installers only
•
The gas appliance and vent system must be vented directly to the outside of the building, and never be at-
tached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance
must use it's own separate vent system.
•
Make sure the exhaust pipe on the heater connects to the exhaust portion of the cap. The illustration in Figure
4 shows how the flex liners should be attached.
•
The exhaust vent must reline the entire length of the chimney and terminate above the chimney top.
•
Be careful not to crimp or rupture the liner when bending it into chimney offsets.
•
When installed, the vent must meet all of the vent manufacturer's requirements
•
Make sure to order the following:
•
Simpson Dura-Vent Chimney Liner Flex Extension (part #2280).
•
Simpson Dura-Vent Chimney Liner Termination Kit (part #923GK).
•
Simpson Dura-Vent High Wind Termination Cap (part #991).
Figure 4