Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-72
I/O modules PCD1|PCD2
PCD2.W3x0
5
Formulae for temperature measurement
For Ni 1000 (PCD2.W340)
Validity: Temperature range - 50 … + 210 °C
Computational error:
± 0.5 °C
T= - 188.5 +
260 • DV
2616
- 4.676 • 10
-6
• (DV - 2784)
2
For Pt 1000 (PCD2.W340)
Validity: Temperature range - 50 … +400 °C
Computational error:
± 1.5 °C
T= - 366.5 +
450 • DV
2474
+ 18.291 • 10
-6
• (DV - 2821)
2
Resistance measurement up to 2.5 kΩ
(PCD2.W340)
Special temperature sensors or any other resistances up to 2.5 kΩ can be con
-
nected to the PCD2.W340. The digital value can be calculated as follows:
DV= 16 380 • R
(7 500 + R)
where 0 ≤ DV ≤ 4095 and R=the resistance to be measured in Ω.
For Ni 100 (PCD2.W350)
Validity: Temperature range - 50 … +250 °C
Computational error:
± 1.65 °C
T= - 28.7 +
300 • DV
3628
- 7.294 • 10
-6
• (DV - 1850)
2
For Pt 100 (PCD2.W350)
Validity: Temperature range - 50 … +600 °C
Computational error:
± 1 °C
T= - 99.9 +
650 • DV
3910
+ 6.625 • 10
-6
• (DV -2114)
2
For Pt 1000 (PCD2.W360)
Validity: Temperature range - 50 … +150 °C
Computational error:
± 0.25 °C
T= - 178.1 +
200 • DV
2509
+ 3.873 • 10
-6
• (DV -2786)
2
T = temperature
DV = digital value