Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-38
I/O modules PCD1|PCD2
PCD2.A220
5
5.5.3
PCD2.A220, 6 relays with make contacts, without contact protection
Application
The module contains 6 relays with normally-open contacts for direct or alternating
current up to 2 A, 250 V
AC
. The module is especially suited wherever AC switching
circuits with infrequent switching have to be controlled. For space reasons, there
is no integrated contact protection. Each group of 3 relays has a common connec-
tion.
Technical data
Number of outputs:
3 + 3 make contacts with common terminal
Type of relay (typical):
RE 030024, SCHRACK
Switching capacity:
(contact lifetime)
2 A, 250 VAC AC1
0.7 × 10
6
operations
1 A, 250 VAC AC11
1.0 × 10
6
operations
2 A, 50 VDC DC11
0.3 × 10
6
operations
3)
1 A, 24 VDC DC11
0.1 × 10
6
operations
1)3)
Relay coil supply:
2)
nominal 24 VDC smoothed or pulsed,
8 mA per relay coil
Voltage tolerance, dependent on
ambient temperature:
20 °C: 17.0 … 35 VDC
30 °C: 19.5 … 35 VDC
40 °C: 20.5 … 32 VDC
50 °C: 21.5 … 30 VDC
Output delay:
typically 5 ms at 24 VDC
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
(from +5 V bus)
1 … 20 mA
typically 10 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
max. 48 mA
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
1)
With external protective diode
2)
With reverse voltage protection
3)
These ratings are not UL-listed
In the appendix, Chapter A.4 relay contacts, are calculation data and wiring sug-
gestions for the relay contacts. These data should be absolutely considered for
safe switching and a long life span of the relays.