Digital input modules, electrically isolated from the I/O Bus
6
6.3
Digital input modules, electrically isolated from the I/O Bus
PCD3.E500
6 inputs for 115
…
230 V
AC
PCD3.E610
8 inputs 24 V
DC
, 10 ms
PCD3.E613
8 inputs 48 V
DC
,
9 ms
Electrical isolation of inputs to the Saia PCD
®
.
The channels are not isolated from each other
Definition of input signals
for 5 V
DC
for 24 V
DC
for 48 V
DC
(on request)
PCD3.E610
PCD3.E613
7 V
DC
5 V
DC
2.5 V
DC
0 V
DC
1 V
DC
-7 V
DC
1
0
30 V
DC
24 V
DC
15 V
DC
0 V
DC
5 V
DC
-30 V
DC
1
0
60 V
DC
48 V
DC
30 V
DC
0 V
DC
10 V
DC
-60 V
DC
1
0
for 115 – 230 V
AC
PCD3.E500
1
0
250 V
AC
80 V
AC
40 V
AC
0 V
AC
Installation instructions
For reasons of safety it is not permissible to connect low voltages (up to 50V)
and higher voltages (50
…
250 V) to the same module.
If a Saia PCD
®
module is connected to a higher voltage (50
…
250 V), approved
components for this voltage must be used for all elements that are electrically con-
nected to the system.
Using higher voltage (50…250V), all connections to the relay contacts must be
connected on the same circuit, i.e. in such a way that they are all protected against
one AC phase by one common fuse. Each load circuit may however be fused
individually.
I/O modules and I/O terminal blocks may only be plugged in and removed when the
Saia PCD
®
and the ex24V are disconnected from the power supply.