Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-94
I/O modules PCD1|PCD2
PCD2.W5x0
5
Internal current
consumption:(from +5 V bus)
max. 200 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
0 mA
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
As the current consumption of this module is considerable, when using a number
of them in the same system, the total load for all modules must be taken into
consideration.
Terminals
Bus connector
DC-DC converter
Basic module
Jumper: inputs unipolar (U)
Substitution module
Jumper U/B 0 and U/B 1
on substitution module
Jumper: inputs bipolar (B)
Screw terminals
+ must not be connected
9
8
7
6
5
4
3
2
1
0
+A1
-A1
+A0
-A0
+E1
-E1
+E0
-E0
U/B0 U/B1
The negative terminals “–” of outputs are connected internally to the ground, each
via a 100 Ω resistor.
Analogue/digital values
Inputs
Input signals
Digital values
Classic
xx7
Simatic
unipolar
bipolar
unipolar
bipolar
unipolar
bipolar
+10 V
4095
4095
4095
4095
27648
27648
+5 V
2047
3071
2047
3071
13824
13824
0 V
0
2047
0
2047
0
0
-5 V
0
1023
0
1023
0
-13824
–10 V
0
0
0
0
0
-27648
Outputs
Digital values
Output signals
Classic
xx7
Simatic
unipolar
bipolar
4095
4095
27648
+10.0 V
+10.0 V
3071
3071
20736
+7.5 V
+ 5.0 V
2047
2047
13824
+5.0 V
0 V
1023
1023
6912
+2.5 V
-5.0 V
0
0
0
0 V
–10.0 V