Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-62
I/O modules PCD1|PCD2
PCD2.W2x0
5
Terminals
Bus connector
Bus interface
Reference voltage (and source)
A/D converter and multiplexer
Input filter
Screw terminals
9
8
7
6
5
4
3
2
1
0
E0
1
2
3
4
5
6
E7
Digital/analogue values
Input signals and type
Digital values
PCD2.W200
PCD2.W210
PCD2.W220
Classic
xx7
Simatic
+ 10.0 V
+ 20 mA
Calculate the
appropriate
values with the
formulae at
the end of this
section
1023
1023
27648
+ 5.0 V
+ 10 mA
512
512
13824
+ 4 mA
205
205
5530
0 V
0 mA
0
0
0
–
10.0 V
–
20 mA
0
0
0
Connection concept PCD2.W200
9
8
7
6
5
4
3
2
1
0
-
E7
E6
E5
E4
E3
E2
E1
E0
-
PGND
PCD2/3.W200
Earthing bar
Shield
Signal source 0…10 V
Signal source 0…10 V
Signal source 0…10 V
Signal source 0…10 V
max. 25 cm min. 2.5 mm
2
Power PCD
Shield
Shield
Shield