Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-103
I/O modules PCD1|PCD2
PCD2.W525 Combined analogue input/output module with galvanic isolation
5
Signification of the I/O words of a PCD2/3.W525 module?
When configuring a W525 module using the Device Configurator or the Profi-S-I/O
(or Profibus DP) Network Configurator, the PCD2/3.W525 does need two registers
for the analogue outputs and 8 registers for the analogue inputs.
The significations of the registers are the following:
Output registers:
Register
Bit 31
…
16
Bit 15
…
0
n
Value CH0 Output
n+1
Value CH1 Output
Description of the output registers:
Value CH0..1 (Register n, n+1)
This registers (Bit 0 to 15) does contain the analogue output value of the corre-
sponding analogue output. It’s a 12 Bit value.
Input registers:
Register
Bit 31
…
16
Bit 15
…
0
n
Value CH0 Input
n+1
Value CH1 Input
n+2
Value CH2 Input
n+3
Value CH3 Input
n+4
Load Current/Voltage
n+5
Status Module
n+6
Status Input
n+7
Status Output
Description of the input registers:
Value CH0
…
CH3 (Register n
…
n+3)
This registers (Bit 0 to 15) does contain the analogue input value of the corre-
sponding analogue input. It’s a 14 Bit value.
Load_Current / Load_Voltage (Register n+4)
On this register (Bit 0 to 15) the actual current or voltage value is displayed.
■ current in [μA] (0
…20’000)
■