Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-121
I/O modules PCD1|PCD2
PCD2.H210
5
5.18.1
PCD2.H210, Motion control module for stepper motors
Application
The PCD2.H210 Module provides fully autonomous control and monitoring of
stepper motor travel, with run-up and braking ramps. The commands for stepper
motor motion cycles are transmitted to the module by function blocks in the user
program.
During motion, the SM processor monitors the frequency profile and the accelera
-
tion and braking ramps to move the axis to the destination position without loss of
steps. Each module controls an independent axis. The module supplies a mono-
phase pulse string which is conveyed to a suitable electronic drive. The module
has 4 inputs and 4 outputs.
Technical data
Number of axes:
1
Positioning distance (counting
range):
0 … 16,777,215 (24 bit)
Frequency ranges (selecta-
ble) *):
9.5 … 2,431 Hz
19 … 4,864 Hz
38 … 9,727 Hz
76 … 19,454 Hz
Acceleration *):
0.6 … 1224 kHz/s, non-linear range division depending on
the selected frequency range
Profile generator:
with symmetrical acceleration and braking ramps
Data protection:
All data in this module are volatile
(non-volatile Saia PCD
®
registers are available).
Digital inputs
Number of inputs:
Terminal 0 = E0
Terminal 1 = E1
Terminal 2 = E2
Terminal 3 = E3
4
configurable as emergency stop or for general use
configurable as limit switch LS1 or for general use
configurable as reference switch or for general use
configurable as limit switch LS2 or for general use
Nominal voltage:
24 VDC
“low” range:
-30 … +5 V
“high” range:
+15 … 30 V
for source operation only,
for safety reasons, normally-closed contacts (negative
logic) should be used
Input current:
typically 6.5 mA
Input filer:
< 1ms
Circuit type:
electrically connected
Digital outputs
Number of outputs:
Terminal 4
A0:
Terminal 5
A1:
Terminal 6
A2:
Terminal 7
A3:
4
Output “PUL” (pulses for motor)
Output “DIR” (direction of motor rotation)
programmable as required
programmable as required
Switching capacity:
0.5 A each in the range 5 … 32 V, residual ripple max. 10 %
Short circuit protection:
no
Electrical isolation:
no