2 GPRS-T6
SATEL
4 OC type outputs (programmed as NO or NC), controlled:
– locally – by means of inputs;
– remotely – by means of SMS messages or CLIP.
Ability to control the outputs from 64 telephones using the CLIP service.
High-current (0.5 A) output, with polymer fuse, to perform the function of power supply
output (optionally, it can perform the power input function).
Information on the status of supervised equipment and module through reporting in
Contact ID format (GPRS, SMS) or messaging (SMS, CLIP).
Encrypted transmission of events sent with the use of GPRS technology (TCP or UDP
protocol).
Capability to automatically replace the GPRS transmission with SMS message, if there are
problems with GPRS transmission.
Periodical test transmissions for checking availability of the module:
– to selected telephone numbers (with the use of SMS message or CLIP service);
– to monitoring stations.
Capability of generating additional test transmissions:
– after identification of the calling party's telephone number (CLIP service);
– after receiving command from the GPRS-S
OFT
program.
Option to check the status of available resources and account validity of the SIM card
installed in the module.
Indicator of GSM signal level received by industrial cellular telephone and an indicator of
troubles connected with logging into the GSM network.
Module configuration:
– locally – through the RS-232 (TTL) port;
– remotely – through the GSM network (GPRS technology);
– remotely – by means of SMS messages.
Capability of remotely updating the module firmware by means of GPRS.
Ability to automatically restart the module.
Switching power supply, output current 2 A with short-circuit protection, provided with a
battery status supervision and low battery disconnect system.
Powered with 18 V AC (±10%).
Possibility to power with 12 V DC.
2. Description of electronics board
Description of terminals:
+12V
- DC power output / input (12 V DC ±15%).
AC
- AC power input (18 V AC ±10%).
COM
-
common
ground.
Z1 ÷ Z8
-
inputs. They can be programmed as digital (NC or NO type) or analog ones.
01 ÷ 04
- OC type outputs.
BTE
- digital input programmable as NC or NO (it can supervise e.g. the battery of
additional power supply unit).
TMP
- digital input programmable as NC or NO (it can supervise e.g. the tamper
contact of module enclosure etc.).
ACE
- input for testing AC voltage presence (up to 25 V AC).